Of the leakage current measured online on an SPD, how much is normal and how much is the real signal of MOV ageing? The answer: the SPD leakage consists of a capacitive component roughly in phase with

2026-10-18 Smart Lightning Protection FEXLINK Research 8 min
The Resistive Component of SPD Leakage Current: Why It Exposes MOV Aging Earlier
The Resistive Component of SPD Leakage Current: Why It Exposes MOV Aging Earlier

Direct Answer

Of the leakage current measured online on an SPD, how much is normal and how much is the real signal of MOV ageing? The answer: the SPD leakage consists of a capacitive component roughly in phase with the voltage and a resistive component tied to the resistance; the capacitive part drifts normally with grid voltage and temperature, while the resistive part rises significantly only as the MOV ages (grain-boundary breakdown, developing leakage paths). Separating the resistive component and watching its trend detects degradation earlier and more accurately than watching total leakage, and it also reduces false alarms.

At a distribution room, a total-leakage threshold alarm on one SPD kept tripping during the summer as the total drifted past the threshold; bench-testing with a resistive-current tester showed the resistive component had only risen slightly and the MOV was not degraded. After switching the monitoring to resistive-component trend judgment, the false alarms stopped, and another SPD that was truly ageing was caught early. The key distinction: total leakage = capacitive + resistive — the capacitive part drifts normally with the environment, and a rising resistive part is the real ageing signal; looking at the total lets temperature and voltage mislead you, while separating the resistive component gives a true reading.

Why:

- Two components: the capacitive part is roughly in phase with the voltage (normal); the resistive part is tied to the resistance (ageing signal); - Why the capacitive part drifts: the MOV junction capacitance changes with voltage and temperature — normal fluctuation; - How ageing shows up: grain-boundary breakdown and developing leakage paths → a significant rise in the resistive component; - μA-level precision: the two components often differ by only tens of μA; without enough precision you cannot separate them.

Key insight: "The capacitive component is the shadow of the environment; the resistive component is the microphone of ageing — separate it and watch the trend to catch degradation earlier and more accurately."

At a data centre, total leakage was recorded monthly and stayed flat for a year, triggering no alarm; a routine check with a resistive-current analyser found the resistive component had been rising for three consecutive months, near the knee point. After replacing the SPD, the resistive component fell back. Lesson: a flat total can mask a quietly rising resistive component — only separation leaves ageing nowhere to hide.

1. The Two Components of Total Leakage: Capacitive vs Resistive

Step one: leakage is not "one number".

The capacitive component (the larger share): - The MOV behaves capacitively (junction capacitance); - The current leads the voltage by about 90°; - Its magnitude varies with voltage and temperature; - It is always present in normal operation.

The resistive component (the smaller share): - The MOV grain boundaries conduct resistively; - The current is roughly in phase with the voltage; - Its magnitude rises significantly with ageing; - It is the "sensitive indicator" of degradation.

Why separate them: - Total leakage = capacitive + resistive (vector sum); - The capacitive component masks the resistive change (larger share); - Looking at the total alone, a small resistive rise is invisible; - After separation, the resistive trend becomes clear.

Key insight: "Leakage is the sum of two vectors — the capacitive part is large, the resistive part small; without separation, the small part's deterioration is hidden by the large part."

2. Why the Capacitive Component Drifts with Voltage and Temperature

Step two: why environmental changes make the total "lie".

The effect of voltage: - Grid voltage fluctuates (±10% is normal); - The MOV junction capacitance changes with voltage; - The capacitive leakage follows the voltage; - Higher voltage → higher leakage (not ageing).

The effect of temperature: - Higher temperature → higher leakage; - The junction capacitance has a temperature coefficient; - Summer leakage is generally higher; - The temperature effect is easily confused with ageing.

Effect on the total: - The total drifts "normally" with the environment; - Threshold alarms mis-operate (in summer); - Real ageing is masked by the drift; - The total alone cannot distinguish.

Key insight: "The capacitive component follows voltage and temperature — a summer 'leakage exceedance' may just be heat, not damage."

3. How MOV Ageing Shows Up in the Rising Resistive Component

Step three: the physical process of ageing.

MOV ageing mechanism: - Grain boundaries degrade under long-term voltage stress; - Boundaries break down, forming leakage paths; - The resistive leakage increases; - Path expansion → accelerated ageing (thermal-runaway risk).

Behaviour of the resistive component: - Early ageing: small resistive rise (below threshold); - Mid-stage: continuous rise (clear trend); - Late stage: significant increase (near end of life); - The resistive rise precedes any "perceptible" change in the total.

Why "earlier": - The resistive share is small; early changes do not affect the total's appearance; - After separation, tiny rises can be identified as a trend; - Early detection → early replacement; - Avoid developing into thermal runaway.

Key insight: "Ageing starts at the grain boundaries — the resistive component is a direct reading of the boundary state; a rising trend is ageing speaking."

4. What Separating the Resistive Component Means for Fewer False Alarms

Step four: fewer false alarms, earlier detection.

Sources of false alarms: - Total-leakage threshold + environmental drift → summer false alarms; - False alarms make operations "cry wolf"; - Widening the threshold → real ageing is missed; - A dilemma.

The resistive-component approach: - Watch only the resistive trend, not the capacitive fluctuation; - Environmental drift does not trigger (normal fluctuation filtered); - Real ageing must trigger (rising trend); - Fewer false alarms and fewer missed detections.

Engineering effect: - More accurate alarms (less manual review); - Earlier ageing detection (a wider replacement window); - More credible data (the trend is explainable); - Operations focus on real problems.

Key insight: "Separating the resistive component filters out environmental noise and amplifies the ageing signal — fewer false alarms, yet earlier detection."

5. Why Online Monitoring Needs μA-Level Precision to Separate the Two

Step five: measurement precision is the precondition for separation.

Why it is hard: - The capacitive component is the main quantity (tens to hundreds of μA); - The resistive component is small (a few to tens of μA); - Both are summed in the total leakage; - Without enough precision, separation is impossible.

μA-level precision: - Requires synchronously sampling the voltage and current phase; - Computes the in-phase component (resistive) and the quadrature component (capacitive); - μA-level resolution is needed to recognise early changes; - This is the technical precondition for "separation".

Engineering requirements: - Sensor range and resolution matched; - Phase synchronisation (voltage reference); - Temperature compensation (distinguish environment from ageing); - Trend algorithms (baseline + knee point).

Key insight: "You can only separate what you can measure — without μA-level precision and phase synchronisation, the resistive component is invisible."

6. Product Implementation: Intelligent Lightning-Protection Online Monitoring

WeiWuLian products put resistive separation into practice:

- FS/ESM SPD Monitor: synchronously samples voltage/current phase and separates capacitive/resistive components; - FSS Intelligent SPD: built-in monitoring with self-diagnosis; - Platform trend analysis: resistive-component baseline + knee-point alarms; - Temperature compensation: filters environmental drift and reduces false alarms.

The design principle in one sentence: "Separate the resistive component, watch the trend, set the knee point — ageing detected earlier, false alarms greatly reduced."

7. Common Misjudgments

1. "Total-leakage exceedance means ageing": summer capacitive drift also exceeds. Result: frequent false alarms. Correct: judge by the separated resistive component. 2. "A flat total means safe": the resistive part rises quietly and is masked. Result: ageing missed. Correct: track the resistive trend. 3. A fixed threshold on the total: not corrected for the environment. Result: a dilemma (false/missed alarms). Correct: resistive trend + knee point. 4. "Leakage measurement" without phase synchronisation: the two parts cannot be separated. Result: the measurement is useless. Correct: μA-level + phase separation. 5. No temperature compensation: environmental drift treated as ageing. Result: unreliable alarms. Correct: compensate, then watch the trend.

Scope and Limitations

This article explains the capacitive/resistive composition of SPD leakage, why the capacitive part drifts with the environment, the principle of the resistive component as an MOV-ageing signal, and the value of separation for fewer false alarms, applicable to SPD online-monitoring selection and data interpretation. The quantitative threshold and knee point of the resistive component depend on the SPD type, manufacturer data and on-site voltage/temperature; follow GB/T 18802.11 and the product manual, determined by professional operations. All cases are anonymized (a distribution room, a data centre) and do not refer to any specific customer.

FAQ

Of the leakage current measured online on an SPD, how much is normal and how much is the real signal of MOV ageing? The answer: the SPD leakage consists of a capacitive component roughly in phase with
Of the leakage current measured online on an SPD, how much is normal and how much is the real signal of MOV ageing? The answer: the SPD leakage consists of a capacitive component roughly in phase with the voltage and a resistive component tied to the resistance; the capacitive part drifts normally with grid voltage and temperature, while the resistive part rises significantly only as the MOV ages (grain-boundary breakdown, developing leakage paths). Separating the resistive component and watching its trend detects degradation earlier and more accurately than watching total leakage, and it also reduces false alarms.