Integrated Power Monitoring Device (ZSA)
ZSA-31331-R
Power monitoring device with full-wave and harmonic analysis, independent bidirectional energy metering, event and extreme-value logging, and an IP52 front panel.

Product Overview
Power monitoring device with full-wave and harmonic analysis, independent bidirectional energy metering, event and extreme-value logging, and an IP52 front panel.
Core capabilities
Full-wave and harmonic analysis: Three-phase voltage, current, power and individual harmonic parameters.. Independent bidirectional energy: Forward and reverse active and reactive energy accumulated separately.. Digital inputs and outputs: 2DI+2DO or 7DI+2DO, programmable..
Data Generated
Product Features
Full-wave and harmonic analysis
Three-phase voltage, current, power and individual harmonic parameters.
Independent bidirectional energy
Forward and reverse active and reactive energy accumulated separately.
Digital inputs and outputs
2DI+2DO or 7DI+2DO, programmable.
High-speed MODBUS communication
RS485 with physical isolation, 1200~38400bps.
Event and extreme logging
Events, extremes, maximum demand, 24-hour curve, 30-day peaks.
Dot-matrix LCD
26 pages of electrical parameters for on-site checking.
System Topology
Technical Parameters
Technical Data
Wiring Three-phase three-wire, three-phase four-wire Voltage range AC 5~500V, overload 1.2 times continuous / 2 times for 1s Current range AC 20mA~5A, overload 1.2 times continuous / 10 times for 5s Frequency 45 ~ 65Hz Power supply AC220V / AC85~265V / DC100~300V, ≤5VA Energy pulse 1 channel, constant 8000imp/kWh
| Wiring | Three-phase three-wire, three-phase four-wire |
| Voltage range | AC 5~500V, overload 1.2 times continuous / 2 times for 1s |
| Current range | AC 20mA~5A, overload 1.2 times continuous / 10 times for 5s |
| Frequency | 45 ~ 65Hz |
| Power supply | AC220V / AC85~265V / DC100~300V, ≤5VA |
| Energy pulse | 1 channel, constant 8000imp/kWh |
| Communication | RS485, MODBUS-RTU, 1200~38400 |
| Digital output | 3A/250VAC, 3A/30VDC |
| Measurement class | Electrical quantities 0.5; active energy 0.5; reactive energy 1.0 |
| Display | Dot-matrix LCD, 26 pages of electrical parameters |
| Operating temperature | -10℃ ~ +45℃ |
| Degree of protection | Front panel IP52 |
Installation Instructions
Standard 35 mm DIN rail mounting; terminals: supply side L1/L2/L3, N, PE, communication and signal terminals as marked on the device.
Key Points
FAQ
Related Products

ESA Full-Factor Smart Meter (Rail-Mount)
Rail-mount installation, synchronous acquisition of voltage/current/power/harmonics, 256 samples/cycle, the energy-data base for energy supervision.

ESA Embedded Multi-Function Energy Meter
Class 0.2 accuracy, 2nd-31st harmonic analysis, embedded panel mounting, for cabinet fine-grained metering and efficiency analysis.

ESE Power-Quality Monitor
Comprehensive power-quality monitoring including harmonics, voltage deviation, frequency deviation and three-phase unbalance, for efficiency analysis.
Learn MoreIntegrated Power Monitoring Device (ZSA) Application Scenarios
Contact us for detailed solutions, quotes and technical support.