Arc Fault Detector (FA)
FA-1011-R
Detects parallel and series arc faults with local sound and light alarm and platform upload. Overvoltage, undervoltage and overcurrent thresholds are adjustable, and 5000 events are logged.

Product Overview
Detects parallel and series arc faults with local sound and light alarm and platform upload. Overvoltage, undervoltage and overcurrent thresholds are adjustable, and 5000 events are logged.
Core capabilities
Dual arc detection: Parallel and series arcs both identified, reducing false alarms.. Local sound and light alarm: Audible and visual warning issued as soon as an arc is detected.. RS485 alarm upload: RS485 standard, with alarms reported to the supervisory system..
Data Generated
Product Features
Dual arc detection
Parallel and series arcs both identified, reducing false alarms.
Local sound and light alarm
Audible and visual warning issued as soon as an arc is detected.
RS485 alarm upload
RS485 standard, with alarms reported to the supervisory system.
Electrical parameter protection
Overvoltage, undervoltage and overcurrent thresholds are configurable.
Event log storage
The most recent 5000 events are retained for traceability.
DIN rail mounting
Standard 35mm DIN rail, installed inside the enclosure.
System Topology
Technical Parameters
Technical Data
Supply AC230V Power consumption ≤1W during normal monitoring Monitored load AC63A and below Overvoltage protection 200~300V adjustable (factory 260V) Undervoltage protection 100~187V adjustable (factory 160V) Overcurrent protection 5~63A adjustable (factory 32A)
| Supply | AC230V |
| Power consumption | ≤1W during normal monitoring |
| Monitored load | AC63A and below |
| Overvoltage protection | 200~300V adjustable (factory 260V) |
| Undervoltage protection | 100~187V adjustable (factory 160V) |
| Overcurrent protection | 5~63A adjustable (factory 32A) |
| Arc detection | Arc current 3A factory setting; arc count 2~30 adjustable (factory 10) |
| Event log | Most recent 5000 events |
| Communication | RS485, 9600bps |
| Digital output | Dry normally-open contact AC250V/5A, DC30V/5A (custom) |
| Operating temperature | -10℃ ~ +55℃ |
| Applicable standard | GB 14287.4-2014 |
Installation Instructions
Standard 35 mm DIN rail mounting; terminals: supply side L1/L2/L3, N, PE, communication and signal terminals as marked on the device.
Key Points
FAQ
Related Products

ESA Full-Factor Smart Meter (Rail-Mount)
Rail-mount installation, synchronous acquisition of voltage/current/power/harmonics, 256 samples/cycle, the energy-data base for energy supervision.

ESA Embedded Multi-Function Energy Meter
Class 0.2 accuracy, 2nd-31st harmonic analysis, embedded panel mounting, for cabinet fine-grained metering and efficiency analysis.

ESE Power-Quality Monitor
Comprehensive power-quality monitoring including harmonics, voltage deviation, frequency deviation and three-phase unbalance, for efficiency analysis.
Learn MoreArc Fault Detector (FA) Application Scenarios
Contact us for detailed solutions, quotes and technical support.